RAV-GM2803AT8P-E
TOSHIBA - BIG DI 3ph
Certificate:
18.06.008
Model Type:
AC2/A/M/R
Manufacturer:
Carrier RLC Europe SAS
Mounting:
Floor standing
Cooling Performance
PdesigncDesign cooling capacity at 35°C outdoor, 27°C indoor, 100% load. More
23.50 kW
SEERSeasonal Energy Efficiency Ratio - annual cooling efficiency. Higher is better. A+++ requires ≥8.5. More
5.12
EEREnergy Efficiency Ratio at 35°C outdoor (Condition A, 100% load). More
2.23
PcRated cooling capacity at standard test conditions.
23.50 kW
QceEstimated annual electricity consumption for cooling (kWh/year).
0 kWh
Heating Performance
PdesignhDesign heating capacity at -10°C outdoor (bivalent point). More
12.30 kW
SCOPSeasonal Coefficient of Performance - annual heating efficiency. A+++ requires ≥5.1. More
3.53
COPCoefficient of Performance at +7°C outdoor (standard rated conditions). More
2.48
PhRated heating capacity at standard test conditions.
24.00 kW
QheEstimated annual electricity consumption for heating (kWh/year).
0 kWh
Estimated Annual Running Cost
€
/kWh
Cooling
0 kWh/yr
Heating
0 kWh/yr
StandbyAnnual standby consumption: (Psbc + Psbh) × 8760h / 1000
613 kWh/yr
Total
613 kWh/yr
Heating Partial Load
Cooling Partial Load
Efficiency Ratings
Climate Zone SCOPAverage=typical European climate, Colder=Scandinavian, Warmer=Mediterranean.
SCOP
Acoustic Levels (dB)Sound power levels in dB(A). Lower is quieter. Note: sound power ≠ sound pressure. At 1m distance, sound pressure is typically 10-15 dB lower. More
Outdoor
78 dB — Very loud
Indoor 1
67 dB — Loud
Indoor 2
67 dB — Loud
Operating Limits & Bivalent PointTOL = manufacturer-declared minimum operating temperature (often conservative — actual capability may be lower). Tbiv = outdoor temperature below which the heat pump alone can no longer cover its rated heating output, meaning supplemental heating may be needed. More
TOL (Operating Limit)
-10.0°C
Tbiv (Bivalent Point)
-10.0°C
Ph at TOLHeating capacity at the temperature operating limit.
12.30 kW
COP 1.93
Ph at TbivHeating capacity at the bivalent temperature.
12.30 kW
COP 1.93
TOL -10°
Tbiv -10°
-25°C
-10°C (design)
+7°C (rated)
+20°C
Standby & Off-Mode Power
Cooling Mode
| Standby (Psbc) | 35.0 W |
| Off mode (Poffc) | 35.0 W |
| Thermostat off (Ptoc) | 29.0 W |
| Crankcase heat (Pckc) | 0.0 W |
Heating Mode
| Standby (Psbh) | 35.0 W |
| Off mode (Poffh) | 35.0 W |
| Thermostat off (Ptoh) | 64.0 W |
| Crankcase heat (Pckh) | 0.0 W |
General Specifications
Refrigerant:
R32
Factory ChargePre-filled refrigerant amount. Additional charge may be needed for longer pipe runs.
4.6000
Power Supply:
400-3-50
Capacity ControlFixed=single speed, Variable=inverter-driven modulation. More
Variable
Indoor Units:
2
IU Names:
RAV-HM1401FT-E+RAV-HM1401FT-E
Pipe Length:
30.0000
TOLTemperature Operating Limit — manufacturer-declared minimum operating temperature. Often conservative; the unit may operate below this. More
-10.0°C
Full Specifications
Seasonal Efficiency (Cooling) ηs,c:
201.8%
Seasonal Efficiency (Heating) ηs,h:
138.2%
Pec (Electrical Input Cooling):
10.54 kW
Peh (Electrical Input Heating):
9.68 kW
Refrigerant Line:
7.5m
CEE Eligible:
false
IU Range Names:
DI Floor Standing