RAV-GM561ATP-E1/RAV-HM561CTP-E
TOSHIBA - DI
SEER
A+
SCOP
A+
Certificate:
18.06.007
Model Type:
AC1/A/S/R
Manufacturer:
Carrier RLC Europe SAS
Mounting:
Ceiling suspended
Cooling Performance
PdesigncDesign cooling capacity at 35°C outdoor, 27°C indoor, 100% load. More
5.00 kW
SEERSeasonal Energy Efficiency Ratio - annual cooling efficiency. Higher is better. A+++ requires ≥8.5. More
5.61
EEREnergy Efficiency Ratio at 35°C outdoor (Condition A, 100% load). More
3.11
PcRated cooling capacity at standard test conditions.
5.00 kW
QceEstimated annual electricity consumption for cooling (kWh/year).
312 kWh
Heating Performance
PdesignhDesign heating capacity at -10°C outdoor (bivalent point). More
2.80 kW
SCOPSeasonal Coefficient of Performance - annual heating efficiency. A+++ requires ≥5.1. More
4.32
COPCoefficient of Performance at +7°C outdoor (standard rated conditions). More
3.90
PhRated heating capacity at standard test conditions.
5.30 kW
QheEstimated annual electricity consumption for heating (kWh/year).
908 kWh
Estimated Annual Running Cost
€
/kWh
Cooling
312 kWh/yr
Heating
908 kWh/yr
StandbyAnnual standby consumption: (Psbc + Psbh) × 8760h / 1000
210 kWh/yr
Total
1430 kWh/yr
Heating Partial Load
Cooling Partial Load
Efficiency Ratings
Climate Zone SCOPAverage=typical European climate, Colder=Scandinavian, Warmer=Mediterranean.
SCOP A+
Acoustic Levels (dB)Sound power levels in dB(A). Lower is quieter. Note: sound power ≠ sound pressure. At 1m distance, sound pressure is typically 10-15 dB lower. More
Outdoor
63 dB — Moderate
Indoor 1
52 dB — Quiet
Indoor 2
Operating Limits & Bivalent PointTOL = manufacturer-declared minimum operating temperature (often conservative — actual capability may be lower). Tbiv = outdoor temperature below which the heat pump alone can no longer cover its rated heating output, meaning supplemental heating may be needed. More
TOL (Operating Limit)
-15.0°C
Tbiv (Bivalent Point)
-7.0°C
Ph at TOLHeating capacity at the temperature operating limit.
3.13 kW
COP 2.24
Ph at TbivHeating capacity at the bivalent temperature.
2.48 kW
COP 2.88
TOL -15°
Tbiv -7°
-25°C
-10°C (design)
+7°C (rated)
+20°C
Standby & Off-Mode Power
Cooling Mode
| Standby (Psbc) | 12.0 W |
| Off mode (Poffc) | 12.0 W |
| Thermostat off (Ptoc) | 6.0 W |
| Crankcase heat (Pckc) | 0.0 W |
Heating Mode
| Standby (Psbh) | 12.0 W |
| Off mode (Poffh) | 12.0 W |
| Thermostat off (Ptoh) | 18.0 W |
| Crankcase heat (Pckh) | 0.0 W |
General Specifications
Refrigerant:
R32
Factory ChargePre-filled refrigerant amount. Additional charge may be needed for longer pipe runs.
1.1000
Power Supply:
230-1-50
Capacity ControlFixed=single speed, Variable=inverter-driven modulation. More
Variable
Indoor Units:
1
IU Names:
RAV-HM561CTP-E
Pipe Length:
20.0000
TOLTemperature Operating Limit — manufacturer-declared minimum operating temperature. Often conservative; the unit may operate below this. More
-15.0°C
Full Specifications
Seasonal Efficiency (Cooling) ηs,c:
0.0%
Seasonal Efficiency (Heating) ηs,h:
0.0%
Pec (Electrical Input Cooling):
1.61 kW
Peh (Electrical Input Heating):
1.36 kW
Refrigerant Line:
7.5 m
CdDegradation coefficient for cycling losses.
0.25
CEE Eligible:
true
IU Range Names:
DI Ceiling